COVID-19 UPDATE - We are still operating so orders will be fulfilled as normal. Some lead times may be affected due to supplier closure but we are endeavouring to ensure minimal disruption to service.

IO/AX4.2 - Output Module

On request
SKU
IO/AX4.2
£40.00 £48.00
The IO/AX 4.2 is a multifunction analogue output module that is designed to convert 1 or 2 x 0-10 volt input signals to 2 or 4 x 0-10
volt outputs. Two AO outputs are operated in sequence from one input with a dead band adjustment of 0 to 1 volt between outputs. The outputs can be individually inverted to operate on 0 to 10 volts or 10 to 0 volts. The inputs and outputs can be selected to operate on 2-10 volts if required.

FEATURES
* 24 volts AC/DC supply
* 2 x Input signals to control 2 x sequenced outputs
* Outputs can operate 0 to 10 or 10 to 0 volts
* Dead band adjustment 1 volts (± 0.5 volts from midpoint VR1 and VR2)
* Inputs and outputs can operate on 0-10 volts or 2-10 volts
* LED Power ON indication
* DIN Rail Mounting
More Information
Description The IO/AX 4.2 converts 1 or 2 x 0-10V input signals to 2 or 4 0-10V outputs. Two AO outputs are operated in sequence from one input with a dead band adjustment of 0 to 1 volt between outputs. The outputs can be individually inverted to operate on 0 to 10 volts or 10 to 0 volts. The inputs and outputs can be selected to operate on 2-10 volts if required. The IO/AX4.1 requires a 24AC or 24DC supply and is compatible with most BMS controllers.
Manuals & Datasheets
 DATA-SHEET 
DATASHEET
Technical Information

SPECIFICATION
Input                                      2 x 0-10 volts or 2-10 volts
Output                                   4 x 0-10 volts or 2-10 volts (rated 5mA each)
                                               AO1 & 2 in sequence
                                               AO2 & 4 in sequence
                                               Outputs can be individually inverted
Power Supply                      24 volts AC or DC (± 15%)
Power Consumption         25mA (max.)
Adjustments                        Dead band AO 1/2 0 to 1 volts (VR1)
                                               Dead band AO 3/4 0 to 1 volts (VR2)
                                               Db is set + and - 0.5 volts across the midpoint
Terminals                             Max. cable size 1.0mm
Operating Temperature      0 to +50ºC
Dimensions                         85mm High
                                                80mm Wide
                                                45mm Deep
Mounting                                DIN Rail

Manufacturer Titan