CM230-L Damper actuator 2 Nm, 75 s, AC 230 V, Open/Close

CM230-L Damper actuator 2 Nm, 75 s, AC 230 V, Open/Close

•    Damper actuator
•    2 Nm, 75 s,
•    AC 230 V, Open/Close, 3-point
•    IP 54, Manual override Gear disengagement with magnet
•    Control with single- / 2-wire contact
•    Connection PVC cable 1m
•    Direction of rotation rotation to the left (ccw)
•    Angle of rotation limit. mechanical integral

SKU: CM230-L

Shipped under 2 days

Excl. Tax: £50.67 Incl. Tax: £60.80

Product Description

Details

Features

  • Simple direct mounting on the damper spindle with a universal spindle clamp (6 ... 12.7 mm). The actuator is then secured with the anti-rotation strap supplied, to prevent it from rotating.

  • Manual override with magnet possible (the gear is disengaged as long as the magnet adheres to the symbol U). The magnet for gear disengagement is integrated in the position indicator.

  • Adjustable angle of rotation with mechanical end stops.

  • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.

    Manuals & Datasheets

    Manuals & Datasheets

    Manuals & Datasheets
     DATA-SHEET 
    DATASHEET
    Technical Information

    •    Nominal voltage AC 100 ... 240 V, 50/60 Hz
    •    Nominal voltage range AC 85 ... 265 V
    •    Power consumption In operation At rest For wire sizing    1.5 W @ nominal torque 1 W 3 VA
    •    Connection Cable 1 m, 3 x 0.75 mm2
    •    Functional data    Torque (nominal torque) Min. 2 Nm @ nominal voltage
    •    Direction of rotation See «Type overview»
    •    Manual override Gear disengagement with magnet
    •    Angle of rotation Without limit With limit Endless Fixed 315° or 0 ... 287.5° with mechanical end stops, can be adjusted in 2.5° increments
    •    Running time 75 s / 90°
    •    Sound power level Max. 35 dB (A)
    •    Position indicator Mechanical, pluggable (with integrated magnet for gear disengagement)
    •    Safety    Protection class II totally insulated
    •    Degree of protection IP54 in any mounting position NEMA2, UL Enclosure Type 2
    •    EMC Low voltage directive CE according to 2004/108/EC CE according to 2006/95/EC
    •    Certification cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
    •    Mode of operation Type 1 (EN 60730-1)
    •    Rated impulse voltage 2.5 kV (EN 60730-1)
    •    Control pollution degree 3 (EN 60730-1)
    •    Ambient temperature –30 ... +50°C
    •    Non-operating temperature –40 ... +80°C
    •    Ambient humidity 95% r.H., non-conde
    •    Maintenance – free

    ManufacturerBelimo