CM230-R Damper actuator 2 Nm, 75 s / 90°, AC 230 V, Open/Close

CM230-R Damper actuator 2 Nm, 75 s / 90°, AC 230 V, Open/Close

•    Damper actuator
•    2 Nm, 75 s,
•    AC 230 V, Open/Close, 3-point
•    IP 54, Manual override Gear disengagement with magnet
•    Control with single- / 2-wire contact
•    Connection PVC cable 1m
•    Direction of rotation rotation to the right (cw)
•    Angle of rotation limit. mechanical integral

On request
SKU
CM230-R
£63.20 £52.67

Features



  • Simple direct mounting on the damper spindle with a universal spindle clamp (6 ... 12.7 mm). The actuator is then secured with the anti-rotation strap supplied, to prevent it from rotating.



  • Manual override with magnet possible (the gear is disengaged as long as the magnet adheres to the symbol U). The magnet for gear disengagement is integrated in the position indicator.



  • Adjustable angle of rotation with mechanical end stops.


  • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.



More Information
Manuals & Datasheets
 DATA-SHEET 
DATASHEET
Technical Information

•    Nominal voltage AC 100 ... 240 V, 50/60 Hz
•    Nominal voltage range AC 85 ... 265 V
•    Power consumption In operation At rest For wire sizing    1.5 W @ nominal torque 1 W 3 VA
•    Connection Cable 1 m, 3 x 0.75 mm2
•    Functional data    Torque (nominal torque) Min. 2 Nm @ nominal voltage
•    Direction of rotation See «Type overview»
•    Manual override Gear disengagement with magnet
•    Angle of rotation Without limit With limit Endless Fixed 315° or 0 ... 287.5° with mechanical end stops, can be adjusted in 2.5° increments
•    Running time 75 s / 90°
•    Sound power level Max. 35 dB (A)
•    Position indicator Mechanical, pluggable (with integrated magnet for gear disengagement)
•    Safety    Protection class II totally insulated
•    Degree of protection IP54 in any mounting position NEMA2, UL Enclosure Type 2
•    EMC Low voltage directive CE according to 2004/108/EC CE according to 2006/95/EC
•    Certification cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
•    Mode of operation Type 1 (EN 60730-1)
•    Rated impulse voltage 2.5 kV (EN 60730-1)
•    Control pollution degree 3 (EN 60730-1)
•    Ambient temperature –30 ... +50°C
•    Non-operating temperature –40 ... +80°C
•    Ambient humidity 95% r.H., non-conde
•    Maintenance – free

Manufacturer Belimo