CM24-L Damper actuator 2 Nm, 75 s, AC / DC 24 V, Open/Close

 CM24-L Damper actuator 2 Nm, 75 s, AC / DC 24 V, Open/Close

•    Damper actuator
•    2 Nm, 75 s,
•    AC / DC 24 V, Open/Close, 3-point
•    IP 54, Manual override Gear disengagement with magnet
•    Control with single- / 2-wire contact
•    Connection PVC cable 1m
•    Direction of rotation rotation to the left (ccw)
•    Angle of rotation limit. mechanical integral

Only 3 left
In stock
SKU
CM24-L
£60.80 £50.67

Features



  • Mode of operation on the damper spindle with a universal spindle clamp (6 ... 12.7 mm). The actuator is then secured with the anti-rotation strap supplied, to prevent it from rotating.


  • Manual override with magnet possible (the gear is disengaged as long as the magnet adheres to the symbol U. The magnet for gear disengagement is integrated in the position indicator.



  • Adjustable angle of rotation with mechanical end stops.



  • High functional reliability actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.



More Information
Manuals & Datasheets
 DATA-SHEET 
DATASHEET
Technical Information

•    Nominal voltage    AC 24 V, 50/60 Hz / DC 24 V
•    Nominal voltage range    AC/DC 19.2 ... 28.8 V
•    Power consumption In operation At rest For wire sizing    0.5 W @ nominal torque 0.2 W 1 VA
•    Connection    Cable 1 m, 3 x 0.75 mm2
•    Torque (nominal torque)    Min. 2 Nm @ nominal voltage
•    Direction of rotation    See «Type overview»
•    Gear disengagement with magnet Angle of rotation Without limit With limit Endless    Fixed 315° or 0 ... 287.5° with mechanical end stops, can be adjusted in 2.5° increments
•    Running time 75 s / 90°
•    Posotion accuracy ±5%
•    Sound power level Max. 35 dB (A)
•    Position indicator Mechanical, pluggable (with integrated magnet for gear disengagement)
•    Protection class III Safety extra-low voltage / UL Class 2 Supply
•    Protection class II totally insulated
•    Degree of protection IP54 in any mounting position NEMA2, UL Enclosure Type 2
•    EMC CE according to 2004/108/EC
•    Certification cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
•    Mode of operationType 1 (EN 60730-1)
•    Rated impulse voltage 0.8 kV (EN 60730-1)
•    Control pollution degree 3 (EN 60730-1)
•    Ambient temperature    –30 ... +50°C
•    Non-operating temperature –40 ... +80°C
•    Ambient humidity 95% r.H., non-condensating (EN 60730-1)
•    Maintenance – free

Manufacturer Belimo