CM24-SR-T-L Damper actuator 2 Nm, 75 s, 95° AC / DC 24 V, modulating

CM24-SR-T-L Damper actuator 2 Nm, 75 s, 95° AC / DC 24 V, modulating

•    Damper actuator
•    2 Nm, 75 s, 95°
•    AC / DC 24 V, modulating
•    IP20, Manual override Gear disengagement with magnet
•    Control DC 0...10 V
•    Operating range DC 2...10 V
•    Position feedback DC 2...10 V
•    Connection Terminals IP20
•    Direction of rotation rotation to the left (ccw)
•    Running direction L (ccw) at Y= 0 V
•    Angle of rotation limit. mechanical integral
•    Spindle driver Clamp 6...12.7 mm

SKU: CM24-SR-T-L

Shipped under 2 days

Excl. Tax: £68.67 Incl. Tax: £82.40
Belimo

Fast next day shipment on stock items

State of the art Helpdesk support

We handle online payments securely

Highly experienced in HVAC products



Product Description

Details

Features

  • Mode of operation The actuator is controlled by means of a standard control signal DC 0 ... 10 V. It opens position dictated by this signal. The measuring voltage U allows the damper position (0 to be electrically indicated and serves as a follow-up control signal for other actuators.

  • Simple direct mounting on the damper spindle with a universal spindle clamp (6 ...The actuator is then secured with the anti-rotation strap supplied, to prevent it from rotating.

  • Manual override with magnet possible (the gear is disengaged as long as the magnet the symbol U . The magnet for gear disengagement is integrated in the position indicator.

  • Adjustable stroke Adjustable angle of rotation with mechanical end stops.

  • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when stop is reached.

  • Home position When the supply voltage is switched on for the first time and after every voltage interruption, synchronisation process is started and the actuator travels to home position (Y = 0 V).

    Manuals & Datasheets

    Manuals & Datasheets

    Manuals & Datasheets
     DATA-SHEET 
    DATASHEET
    Technical Information

    •    Nominal voltage  AC 24 V, 50/60 Hz DC 24 V
    •    Nominal voltage range AC/DC 19.2 ... 28.8 V
    •    Power consumption In operation At rest For wire sizing 1 W @ nominal torque 0.5 W 2 VA
    •    Connection Terminals for 4 x 1.5 mm2 CU wire or 4 x 1.0 mm2 CU litz wires
    •    Torque (nominal torque)    Min. 2 Nm @ nominal voltage
    •    Control Control signal Y Operating range DC 0 ... 10 V, typical input impedance 100 kΩ DC 2 ... 10 V
    •    Position feedback (Measuring voltage U) DC 2 ... 10 V, max. 1 mA
    •    Posotion accuracy ±5%
    •    Direction of rotation See «Type overview»
    •    Angle of rotation Max. 95° , limited on both sides by means of adjustable, mechanical end stops
    •    Running time 75 s / 90°
    •    Sound power level Max. 35 dB (A)
    •    Position indication Mechanical, pluggable (with integrated magnet for gear disengagement)
    •    Protection class III Safety extra-low voltage / UL Class 2 Supply
    •    Degree of protection IP20 in any mounting position NEMA1, UL Enclosure Type 1
    •    Mode of operationType 1 (EN 60730-1)
    •    EMC CE according to 2004/108/EC
    •    Certification cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
    •    Mode of operation Type 1 (EN 60730-1)
    •    Rated impulse voltage 0.8 kV (EN 60730-1)
    •    Control pollution degree 2 (EN 60730-1)
    •    Ambient temperature –30 ... +50°C
    •    Non-operating temperature –40 ... +80°C
    •    Ambient humidity 95% RH, non-condensating (EN 60730-1)
    •    Maintenance – free