CR24-B2 Room temperature controller with 2 sequences AC 24 V Selection mode


CR24-B2 Room temperature controller with 2 sequences AC 24 V Selection mode


•    Room temperature controller with 2 sequences
•    AC 24 V
•    Selection mode, display: AUTO / ECO / MAXIMUM
•    Setpoint: 18...35º C, rotary button: +/- 3 K
•    Temperature sensor: NTC internal 0, external: 10...45º C
•    5 inputs: EHO, Stand-by / ventilation,
•    0 ... 10 V shift, ext. temperature sensor
•    2 outputs: VAV 0 / 2...10 V, heating 3-point
•    Control characteristics: modulating, P-controller,
•    P-Band switchable
•    Housing colour white RAL 9003
•    Base colour light grey NCS 2005 -R 80 B


SKU: CR24-B2

Shipped under 2 days

Excl. Tax: £94.67 Incl. Tax: £113.60
Belimo

Fast next day shipment on stock items

State of the art Helpdesk support

We handle online payments securely

Highly experienced in HVAC products



Product Description

Details

Features

Energy hold off: In energy saving mode, the room temperature is reduced to building protection level, i.e. eitherthe heating setpoint is significantly reduced or the cooling setpoint is significantly increased, forinstance in a room with an open window.

Stand-by: The room temperature is reduced to stand-by level, i.e. either the heating setpoint is slightlyreduced or the cooling setpoint is slightly increased, for instance in a room that is temporarilyunoccupied.

Frost: The frost protection function is activated if the actual room temperature falls below 10°C.

Air flush: The room can be ventilated with the maximum volume flow (max), for instance in order to purge conference rooms, hotel rooms etc.

External temperature sensor: An external temperature sensor can be connected to the analog input ai1, for instance in orderto measure the average room temperature in the exhaust air duct.

External setpoint shift: An external DC 0...10 V signal at the analog input ai2 can be used to shift the basic setpoint 0...10 K, for instance for the summer/winter compensation.

Manuals & Datasheets

Manuals & Datasheets

Manuals & Datasheets
 DATA-SHEET 
DATASHEET
Technical Information

•   Electrical data Nominal voltage AC 24 V 50/60 Hz
•   For wire sizing 3 VA, without actuators
•   Power supply range AC 19.2...28.8 V
•   Connections Terminal block 1...3: 2.5 mm2 Terminal block 4...8: 1.5 mm2
•   Functional data Control characteristics P– P-band heating / cooling Selectable: 1.5 / 1.0 K or 3.0 / 2.0 K
•   External temperature sensor (ai1) Type NTC, 5 kΩ, sensing range 10...45°C for example Belimo type TFK
•   Heating setpoint Range 15...36°C (default 21°C)– Energy hold off Heating 15°C / cooling 40°C– Stand-by Heating –2 K / cooling +3 K
•   Dead band 1 K
•   Frost limit temperature10°C
•   Operation (CR24-B.. only)– Mode switch and status indication (LEDs)AUTO (green) – ECO (orange) – MAX (red)– Rotary knob for setpoint adjustment±3 K
•   Inputs 2 x analog, 3 x digital– External temperature sensor (ai1) Type NTC, 5 kΩ, sensing range 10...45°C– External setpoint shift (ai2) 0...10 V corresponds to 0...10 K– Digital inputs (di1, di2) Contact rating 10 mA
•   Outputs 2 x analog– VAV system output (ao1) (0) 2 ... 10 V, max. 5 mA– Heating output (ao3) 3-point, AC 24 V, max. source current 0.5 A / 10 VA (optimized for actuators with a running time of approx. 150 s)
•   Norms und standards Protection class III Safety extra-low voltage Degree of protectionIP 30 to EN 60529Mode of operation Type 1 to EN 60730-1 Software class A to EN 60730-1 EMC CE conformity to 89/336/EEC
•   Ambient conditions– Operation0...+50°C / 20...90% rH (without condensation– Transport and storage–25...+70°C / 20...90% rH (without condensation
•   Dimensions / Weight Dimensions (H x W x D) 99 x 84 x 32 mm
•   Weight 105 g
•   Housing colors Baseplate CoverNCS2005-R80B light gray(corresponds approx. to RAL 7035)RAL 9003-Signalweiss

ManufacturerBelimo

Reviews