COVID-19 UPDATE - We are still operating so orders will be fulfilled as normal. Some lead times may be affected due to supplier closure but we are endeavouring to ensure minimal disruption to service.

CR24-B2E Room temperature controller with manual operation 2 heating levels, 1 VAV-sequence, AC 24 V Selection mode

On request
SKU
CR24-B2E
£111.33 £133.60

CR24-B2E Room temperature controller with manual operation 2 heating levels, 1 VAV-sequence, AC 24 V Selection mode


•    Room temperature controller with manual operation
•    2 heating levels, 1 VAV-sequence, AC 24 V
•    Selection mode, display: AUTO / ECO / MAXIMUM
•    Setpoint: 18...35º C, rotary button: +/- K
•    Temperature sensor: NTC 10...45º C internal / external
•    5 outputs: EHO, Stand-by / Boost,
•    0...10 V shift, ext. temperature limiter
•    3 outputs: VAV 0/2...10 V,
•    Heating for 1...3 level electric air heater or radiator valve
•    Control characteristics: 2-point and modulating, P-controller
•    Housing colour white RAL 9003
•    Base colour light grey NCS 2005 -R 80 B


More Information
Description

Features

Energy hold off: In energy saving mode, the room temperature is reduced to building protection level, i.e. eitherthe heating setpoint is significantly reduced or the cooling setpoint is significantly increased, forinstance in a room with an open window.

Stand-by: The room temperature is reduced to stand-by level, i.e. either the heating setpoint is slightlyreduced or the cooling setpoint is slightly increased, for instance in a room that is temporarilyunoccupied.

Frost: The frost protection function is activated if the actual room temperature falls below 10°C.

Boost: The room can be ventilated with the maximum volume flow (max) or heated up with themaximum capacity.

Supply air temperature limiter: An optional mounted sensor allows to control the supply air temperature to a maximum of 50°C.

Vmax at heating: For electrical reheaters the air volume at the heating condition can optionally be increased.

Output mode: The do3 output mode can be set accordingly to the application to

                          – stage for one-stage electrical reheater or on/off radiator valve

                          – binary for two-stage electrical reheaters (stage I: ¹/₃, stage II: ²/₃) which will be ¹/₃, ²/₃, ³/₃

Soft start (Roll-out feature): The build-in start-up and roll-out of the stage control provides temperature excess protection. This helps to avoid service calls due to switched-off safety chains and reduces the electrical load after a power-fail.

External setpoint shift: An external DC 0...10 V signal at the analog input ai2 can be used to shift the basic setpoint 0...10 K, for instance for the summer/winter compensation.

Manuals & Datasheets
 DATA-SHEET 
DATASHEET
Technical Information

•   Electrical data Nominal voltage AC 24 V 50/60 Hz
•   For wire sizing 3 VA, without actuators
•   Power supply range AC 19.2...28.8 V
•   Connections Terminal block 1...3: 2.5 mm2 Terminal block 4...8: 1.5 mm2
•   Functional data Control characteristics P– P-band heating / cooling Selectable: 1.5 / 1.0 K or 3.0 / 2.0 K
•   External temperature sensor (ai1) Type NTC, 5 kΩ, sensing range 10...45°C for example Belimo type TFK
•   Heating setpoint Range 15...36°C (default 21°C)– Energy hold off Heating 15°C / cooling 40°C– Stand-by Heating –2 K / cooling +3 K
•   Dead band 1 K
•   Frost limit temperature10°C
•   Operation (CR24-B.. only)– Mode switch and status indication (LEDs) AUTO (green) – ECO (orange) – MAX (red)– Rotary knob for setpoint adjustment±3 K
•   Inputs 2 x analog, 3 x digital – External temperature sensor (ai1) Type NTC, 5 kΩ, sensing range 30...50°C– External setpoint shift (ai2) 0...10 V corresponds to 0...10 K– Digital inputs (di1, di2, di3) Contact rating 10 mA
•   Outputs 1 x analog, 2 x digital – VAV system output (ao1)(0) 2 ... 10 V, max. 5 mA– Heating output (do3), 2 stages Triac, AC 24 V, max. source current 0.5 A / 10 VA
•   Norms und standards Protection class III Safety extra-low voltage Degree of protectionIP 30 to EN 60529Mode of operation Type 1 to EN 60730-1 Software class A to EN 60730-1 EMC CE conformity to 89/336/EEC
•   Ambient conditions– Operation0...+50°C / 20...90% rH (without condensation– Transport and storage –25...+70°C / 20...90% rH (without condensation
•   Dimensions / Weight  Dimensions (H x W x D) 99 x 84 x 32 mm
•   Weight 105 g
•   Housing colors Baseplate Cover NCS2005-R80B light gray (corresponds approx. to RAL 7035) RAL 9003-Signalweiss

Manufacturer Belimo