DRC24A-TP-7 - Rotary actuator 90 Nm, < 90 Nm AC / DC 24 V, Open/Close

DRC24A-TP-7 - Rotary actuator 90 Nm, < 90 Nm AC / DC 24 V, Open/Close



•    Running time motor 35 s / 90°
•    IP 54, Manual override temporary, permanent
•    Connection with terminals

SKU: DRC24A-TP-7

Shipped under 2 days

Excl. Tax: £585.09 Incl. Tax: £702.11

Product Description

Details

Features

  • Simple direct mounting Straightforward direct mounting on the butterfly valve with ISO 5211- F05 assembly flange.
    The mounting position in relation to the butterfly valve can be selected in 90° steps.

  • Manual override Manual override with push-button possible (the gear is disengaged for as long as the button ispressed or remains locked).

  • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when theend stop is reached.

Manuals & Datasheets

Manuals & Datasheets

Manuals & Datasheets
 DATA-SHEET 
DATASHEET
Technical Information

•    Electrical data Nominal voltage AC 24 V, 50/60 Hz / DC 24 V
•    Nominal voltage range AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V
•    Power consumption In operation 9 W @ nominal torque
•    At rest 2 W
•    For wire sizing 12 VA
•    Connection Terminals 4 mm2 (cable Ø 4 ... 10 mm)
•    Parallel operation No
•    Functional data Torque <=90 Nm @ nominal voltage (not constant)
•    Manual override Gearing latch disengaged with push-button, can be locked
•    Running time =35 s / 90°<)
•    Sound power level =62 dB (A) (without butterfly valve)
•    Position indication Yes
•    Safety Protection class III Safety extra-low voltage UL Class 2 Supply
•    Degree of protection IP54 NEMA 2, UL Enclosure Type 2
•    EMC CE according to 2004/108/EC
•    Certification Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14 cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02
•    Mode of operation Type 1
•    Rated impulse voltage 0.8 kV
•    Control pollution degree 3
•    Ambient temperature –30 ... +50°C
•    Medium temperature –20 ... +120°C / +130°C/1 h (in the butterfly valve)
•    Non-operating temperature –40 ... +80°C
•    Ambient humidity 95% r.h., non-condensating
•    Maintenance Maintenance-free
•    Weight Approx. 3.6 kg (without butterfly valve)

ManufacturerBelimo