EVBAT00500 - Battery for EVD reachargeable battery module


The 12v lead backup battery (EVBAT00500) supplies power supply to the driver for the time required to completely close the electronic expansion valve. While during normal operation ensures the battery is correctly recharged.  


TECHNICAL SPECIFICATIONS:

Battery charger power supply: 24 Vac ±15 %
Max battery charge current: 150 mA
Max battery charge voltage: 14 V
Battery used: 12 Vdc hermetic, 1.2 Ah
Charging time: 3 h before starting the system
power supply duration (fixed): 75 s
Output voltage: 22 Vdc ±5 %
Mounting: DIN rail

An optional battery module box frame is available HERE.
SKU: EVBAT00500

Shipped under 14 days

Excl. Tax: £37.49 Incl. Tax: £44.99
Carel

Fast next day shipment on stock items

State of the art Helpdesk support

We handle online payments securely

Highly experienced in HVAC products



Product Description

Details

The EVBAT00300 module is an electronic device made by CAREL which guarantees the temporary power supply to the EVD00004*/EVD000E* driver (up to two drivers can be connected, the maximum current input must not exceed 0.9 A) or EVD000T* (only one driver can be connected), in the case of a sudden power failure.

It signals battery discharged or fault status via an open collector output, which can be used by the EVD000E* driver (EVD evolution, not EVD evolution twin) or the pCO to generate an alarm message and notify the technical service for preventive maintenance.

Powered by a 12 V lead backup battery (EVBAT00500) supplies power supply to the driver for the time required to completely close the electronic valve being controlled, while during normal operation ensures the battery is correctly recharged.