LH230ASR100 - Linear actuator with rack 150 N, 150 s / 100 mm / constant, AC 230 V

LH230ASR100 - Linear actuator with rack 150 N, 150 s / 100 mm / constant,  AC 230 V


•   Modulating Stroke range 0...100 mm
•   IP 54, Manual override by means of push-button
•   Control DC 0...10 V
•   Operating range DC 2...10 V
•   Position feedback DC 2...10 V
•   Connection PVC cable 1m

SKU: LH230ASR100

Shipped under 2 days

Excl. Tax: £98.00 Incl. Tax: £117.60

Product Description

Details

Features

     

    • Manual override Manual operation is possible with the pushbutton (the gearing latch remains disengaged as long as the pushbutton is pressed or detented).         

     

    • Stroke adjustment The stroke of the gear rack can be adjusted on both sides in increments of 20 mm by means of mechanical end stops.

    • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.

    Manuals & Datasheets

    Manuals & Datasheets

    Manuals & Datasheets
     DATA-SHEET 
    DATASHEET
    Technical Information

    •    Electrical data Nominal voltage AC 100 ... 240 V, 50/60 Hz
    •    Power supply range AC 85 ... 265 V
    •    Power consumption In operation 2.5 W @ nominal force At rest 1 W For wire sizing 5 VA
    •    Connection Power supply Cable 1 m, 2 x 0.75 mm2  Signals Cable 1 m, 4 x 0.75 mm2
    •    Functional data Actuating force 150 N @ nominal voltage
    •   Control Control signal Y DC 0 ... 10 V, typical input impedance 100 kΩ
    •   Operating range See «Overview of types»
    •   Position feedback (Measuring voltage U) DC 2 ... 10 V, max. 1 mA
    •   Position accuracy ±5%
    •   Stroke See «Overview of types»
    •   Direction of stroke at Y = 0 V Reversible with switch 1 resp. 0
    •   Running time LH230ASR100/200 150 s / 100 mm
    •   Sound power level <35 dB (A)
    •   Safety Protection class II Totally insulated
    •   Degree of protection IP54 in any mounting position
    •   EMC CE according to 89/336/EEC
    •   Low voltage directive CE according to 73/23/EEC
    •   Mode of operation Type 1 (to EN 60730-1)
    •   Rated impulse voltage Supply 4 kV (to EN 60730-1)
    •   Control 0.8 kV (to EN 60730-1)
    •   Control pollution degree 3 (to EN 60730-1)
    •   Ambient temperature range –30 ... +50°C
    •   Non-operating temperature –40 ... +80°C
    •   Ambient humidity range 95% r.H., non-condensating (to EN 60730-1)
    •   Maintenance Maintenance-free
    •   Dimensions / Weight Dimensions See «Dimensions» on page 3
    •   Weight See «Overview of types»

    ManufacturerBelimo