•   Modulating Stroke range 0...200 mm
•   IP 54, Manual override by means of push-button
•   Operating range DC 2...10 V for stroke 0...200 mm
•   Position feedback DC 2...10 V
•   Connection PVC cable 1m

SKU: LH230ASR200

Shipped under 2 days

Excl. Tax: £100.00 Incl. Tax: £120.00

Product Description

Details

Features

  • Manual override The actuator is controlled by means of a standard control signal DC 0 ... 10 V. It opens to the position dictated by this signal. The measuring voltage U allows the damper position (0 ... 100%) to be electrically indicated and serves as a follow-up control signal for other actuators.

  • Stroke adjustment Manual operation is possible with the pushbutton (the gearing latch remains disengaged as long as the pushbutton is pressed or detented).

  • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.

Manuals & Datasheets

Manuals & Datasheets

Manuals & Datasheets
 DATA-SHEET 
DATASHEET
Technical Information

•    Electrical data Nominal voltage AC 100 ... 240 V, 50/60 Hz
•    Power supply range AC 85 ... 265 V
•    Power consumption In operation 2.5 W @ nominal force At rest 1 W For wire sizing 5 VA
•    Connection Power supply Cable 1 m, 2 x 0.75 mm2  Signals Cable 1 m, 4 x 0.75 mm2
•    Functional data Actuating force 150 N @ nominal voltage
•   Control Control signal Y DC 0 ... 10 V, typical input impedance 100 kΩ
•   Operating range See «Overview of types»
•   Position feedback (Measuring voltage U) DC 2 ... 10 V, max. 1 mA
•   Position accuracy ±5%
•   Stroke See «Overview of types»
•   Direction of stroke at Y = 0 V Reversible with switch 1 resp. 0
•   Running time LH230ASR100/200 150 s / 100 mm
•   Sound power level <35 dB (A)
•   Safety Protection class II Totally insulated
•   Degree of protection IP54 in any mounting position
•   EMC CE according to 89/336/EEC
•   Low voltage directive CE according to 73/23/EEC
•   Mode of operation Type 1 (to EN 60730-1)
•   Rated impulse voltage Supply 4 kV (to EN 60730-1)
•   Control 0.8 kV (to EN 60730-1)
•   Control pollution degree 3 (to EN 60730-1)
•   Ambient temperature range –30 ... +50°C
•   Non-operating temperature –40 ... +80°C
•   Ambient humidity range 95% r.H., non-condensating (to EN 60730-1)
•   Maintenance Maintenance-free
•   Dimensions / Weight Dimensions See «Dimensions» on page 3
•   Weight See «Overview of types»