LH24A-MF200-TP - Linear actuator with rack 150 N, 150 s/100 mm adjustable

LH24A-MF200-TP - Linear actuator with rack 150 N, 150 s/100 mm adjustable AC / DC 24 V


•   Modulating, MFT Stroke range 0...200 mm
•   IP 54, Manual override by means of push-button
•   Control DC 0...10 V , adjustable)
•   Operating range DC 2...10 V,  adjustable
•   Position feedback DC 2...10 V, adjustable
•   Connection terminals IP54

SKU: LH24A-MF200-TP

Shipped under 2 days

Excl. Tax: £90.85 Incl. Tax: £109.02

Product Description

Details

Features

 

  • Mode of operation The actuator is controlled with a standard modulating signal of DC 0 ... 10 V and travels to the position defined by the control signal. Measuring voltage U serves for the electrical display of the damper position 0 ... 100% and as slave control signal for other actuators.

  • Parameterisable actuators The factory settings cover the most common applications. Input and output signals and other parameters can be altered with the MFT-H parameterising device or the BELIMO Service Tool, MFT-P.

  • Simple direct mounting The actuator can be directly connected with the application using the enclosed screws. The head of the gear rod is connected to the moving part of the ventilation application individually on the mounting side or with the Z-KS2 coupling piece provided.

  • Manual override Manual operation is possible with the pushbutton (the gearing latch remains disengaged as long as the pushbutton is pressed or detented).

  • Stroke adjustment  The stroke of the gear rack can be adjusted on both sides in increments of 20 mm by means of mechanical end stops.

  • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.

Manuals & Datasheets

Manuals & Datasheets

Manuals & Datasheets
 DATA-SHEET 
DATASHEET
Technical Information

•     Electrical data Nominal voltage AC 24 V, 50/60 Hz / DC 24 V
•     Nominal voltage range AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V
•     Power consumption In operation 2 W @ nominal force
•     At rest 1.2 W
•     For wire sizing 5 VA
•     Connection Terminals 4 mm2 (Cable Ø 4 ... 10 mm, four-core)
•     Functional data Factory settings 
•     Actuating force Min. 150 N @ nominal voltage
•     Control Control signal Y DC 0 ... 10 V, input impedance 100 k
•     Operating range DC 2 ... 10 V (See also «Overview of types»)
•     Position feedback (Measuring voltage U) DC 2 ... 10 V, max. 0,5 mA
•     Position accuracy ±5%
•     Stroke See «Overview of types»
•     Direction of stroke at Y = 0 V Reversible with switch 1 resp. 0
•     Manual override Gearing latch disengaged with pushbutton, can be locked
•     Stroke adjustment Max. 60, 100, 200 or 300 mm, adjustable in steps of 20 mm, can be limited at both ends with mechanical adjustable end stops
•     Running time LH24A-MF60 90 s / 60 mm
•     LH24A-MF100/200/300 150 s / 100 mm
•     Automatic adjustment of the operating range and the measuring signal U to match the mechanical stroke adjustment -Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool
•     Override control MAX (maximum position) = 100%
•     MIN (minimum position) = 0%
•     ZS (intermediate position, AC only) = 50%
•     Sound power level Max. 35 dB (A)
•     Safety Protection class III Safety extra-low voltage / UL Class 2 Supply
•     Degree of protection IP54 in any mounting position NEMA2, UL Enclosure Type 2
•     EMC CE according to 2004/108/EC
•     Safety Certification cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
•     Mode of operation Type 1
•     Rated impulse voltage 0.8 kV
•     Control pollution degree 3
•     Ambient temperature –30 ... +50°C
•     Non-operating temperature –40 ... +80°C
•     Ambient humidity 95% r.h., non-condensating
•     Maintenance Maintenance-free
•     Dimensions / Weight Dimensions See «Dimensions» on page 5
•     Weight See «Overview of types» on page 1

ManufacturerBelimo