What Our Customers Are Saying
| Product type | Actuator |
| IP rating | IP54 |
| Input Signal | On/Off |
| Manufacturer | Belimo |
| Power Supply | 24Vac/Vdc |
| Torque | 200 N |
| Running time | Quick (2.5 to 20 sec) |
| Actuator type | Linear |
At IACS we provide Free Delivery and Next 1-2 day Delivery for all the Belimo Actuators in stock.
The Belimo SHQ24A100 is an Actuator used in HVAC applications and air ventilation systems.
The Torque force applied by the SHQ24A100 is 200 N.
The power supply requested for this Rotary Actuator is 24Vac/Vdc.
The ideal Belimo Actuators for your system are most affordable at iacs.If you have questions concerning size or installation, refer to the Belimo custom datasheet above or email iacs for individualised support.
SHK24A-SZ100 - CPO linear actuator (with condenser)
• 450 N, 150 s / 100 mm / constant,
• AC / DC 24 V, modulating
• Running time emergency setting position 35 s
• Power-Off-Position adjustable
• Stroke range 0...100 mm
• IP 54, Manual override with push-button
• Control DC 0...10 V
• Operating range DC 0.5...10 V
• Position feedback DC 0.5...10 V
• Connection PVC cable 1m
Features
• Electrical data Nominal voltage AC 24 V, 50/60 Hz / DC 24 V
• Nominal voltage range AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V
• Power consumption In operation 13 W @ nominal torque At rest 2 W For wire sizing 23 VA (I max. 20 A @ 5 ms)
• Connection Cable 1 m, 3 x 0.75 mm2
• Functional data Actuating force Min. 200 N @ nominal voltage
• Direction of stroke Reversible with switch 1 resp. 0
• Manual override Gearing latch disengaged with pushbutton, can be locked
• Stroke adjustment 40 ... 100 mm, adjustable in 20 mm-steps can be limited at both ends with mechanical end stops
• Stroke limiting Min. 40 mm
• Running time 7 s / 100 mm
• Automatic adjustment of operating range to Manual triggering of the adaption by pressing the match the mechanical stroke adjustment «Adaption» button
• Sound power level 52 dB (A)
• Negative torque ! ≤50% from nominal torque (Caution: can only be used with restrictions. Please contact your Belimo representative.)
• Safety Protection class III Safety extra-low voltage UL Class 2 Supply
• Degree of protection IP54 in any mounting position NEMA 2, UL Enclosure Type 2
• EMC CE according to 2004/108/EC
• Certification Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14 cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02
• Mode of operation Type 1.AA
• Rated impulse voltage 0.8 kV
• Control pollution degree 3
• Ambient temperature –30 ... +40°C (no restrictions) +40 ... +50°C (Caution: can only be used with restrictions. Please contact your Belimo representative.)
• NNon-operating temperature –40 ... +80°C
• Ambient humidity 95% r.h., non-condensating
• Maintenance Maintenance-free
• Dimensions See «Dimensions» on page 4
• Weight Approx. 1.25 kg