What Our Customers Are Saying
| Product type | Water Valve |
| Manufacturer | Belimo |
| Flow pattern | 3-Way |
| Valve type | Ball Valve |
| Valve connection | External thread |
| Pressure | PN 40 |
| DN (mm) | DN 10 |
| Temperature range | +5°C to +100°C |
| Flow rate - m³/h | 0.25 kvs |
All in-stock Belimo ball Valves with iacs are delivered for free or within 1-2 days.
The Belimo R505K is a Valve used in HVAC applications (heating, ventilation, and air conditioning) systems as a control or shutdown Valve . in a circuit that is closed.
The Pressure Nominal of this Valve is PN 40.
This R505K Belimo Valve has a 3 port opening connection.
IACS has the most economical Belimo Valves for your system.
If you have any issues about size or installation, please refer to the Belimo custom datasheet above or contact iacs for further information.
Features
• Functional data Flow media Cold and hot water, water with max. 50% volume of glycol
• Temperature of medium +5°C ... +110°C 1), (lower or higher temperatures on request)
• Rated pressure ps see «Type overview»
• Flow characteristic Control path A – AB: equal percentage (to VDI/VDE 2173), n(gl): see «Type overview» Bypass B – AB: linear, flow rate is 70% of kvs value
• Rangeability Sv See «Type overview»
• Leakage rate Control path A – AB: Air bubble-tight (BO 1, DIN3230 T3) Bypass B – AB: Approx. 1...2% of kvs value (in relation to the highest value within the DN (e.g. R513)
• Pipe connector External thread to ISO 228/1
• Differential pressure Δpmax 350 kPa (200 kPa for low-noise operation), Closing pressure Δps 1400 kPa
• Angle of rotation 90°<) (Operating range of control path A – AB 15 ... 90°<), bypass B – AB 15 ... 70°<)
• Installation position Upright to horizontal (in relation to the stem)
• Maintenance Maintenance-free
• Materials Fitting Forged, nickel-plated brass body
• Valve cone and stem Stainless steel
• Stem seal O-Ring, EPDM
• Ball seat PTFE, O-Ring Viton
• Characterizing disk TEFZEL
• Dimensions / Weights see «Dimensions and weights», page 3
• Motorizing see the complete overview of water solutions
• 1)The allowed media temperature can be limited, depending on the type of actuator. The correct values can be found in the corresponding actuator data sheets.