 DATA-SHEET 
DATASHEET
 
Product typeWater Valve
ManufacturerBelimo
Flow pattern3-Way
Valve typeBall Valve
Valve connectionFlanged
PressurePN 6
DN (mm)DN 15
Temperature range+5°C to +100°C
Flow rate - m³/h0.63 kvs

All in-stock Belimo ball Valves with iacs are delivered for free or within 1-2 days.

The Belimo R7015RP63-B1 is a Valve used in HVAC applications (heating, ventilation, and air conditioning) systems as a control or shutdown Valve . in a circuit that is closed.

The Pressure Nominal of this Valve is PN 6.

This R7015RP63-B1 Belimo Valve has a 3 port opening connection.

IACS has the most economical Belimo Valves for your system.

If you have any issues about size or installation, please refer to the Belimo custom datasheet above or contact iacs for further information.

Features

 

  • Mode of operation The characterized control valve is operated by a rotary actuator. The actuator is controlled by a standard modulating or 3-point control system and moves the ball of the valve – the throttling device – to the opening position dictated by the control signal. Open the ball valve counterclockwise and close it clockwise.

  • Flow characteristic Equal-percentage characteristic of the flow rate ensured by the integral characterizing disc.

IACS has the most economical Belimo Valves for your system.


•     Functional data Flow media Cold and hot water, water with max. 50% volume of glycol
•     Temperature of medium +5°C ... +110°C1) (lower or higher temperatures on request)
•     Rated pressure ps see «Type overview»
•     Flow characteristic Control path A – AB: equal percentage (to VDI/VDE 2178) n(gl): see «Type overview» Bypass B – AB: linear, flow rate is 70% of kvs value
•     Rangeability Sv See «Type overview»
•     Leakage rate Control path A – AB: Air bubble-tight (BO 1, DIN3230 T3)Bypass B – AB: Approx. 1...2% of kvs value (in relation to the highest value within the DN (e.g. R713))
•     Pipe connector Flange PN 16 (to EN 1092/1)
•     Differential pressure Δpvmax 100 kPa, Closing pressure Δps 600 kPa
•     Angle of rotation 90°<) (Operating range control path A – AB 15 ... 90°<) ,bypass B – AB 15 ... 70°<) )
•     Installation position Upright to horizontal (in relation to the stem)
•     Maintenance Maintenance-free
•     Materials Fitting Forged, nickel-plated brass body
•     Valve cone and stem Chrome-plated brass
•     Stem seal O-Ring, EPDM
•     Ball seat PTFE, O-Ring Viton
•     Characterizing disk TEFZEL
•     Flange ring DN 15 / 20: Zinc-plated steel DN 25 ... 50: Aluminum
•     Flange joint surface Nickel-plated brass
•     Dimensions / Weights see «Dimensions and weights», page 3
•     Motorizing see the complete overview of water solutions
•     1)The allowed media temperature can be limited, depending on the type of actuator. The correct values can be found in the corresponding actuator data sheets.