SKU
LH24A-SR100

LH24A-SR100 - Belimo Linear actuator with rack 150 N, 150 s / 100 mm / constant, AC / DC 24 V

£160.44 £133.70
On request
Next Supplier Stock Update: 18/10/2026
Free delivery over £30
Manuals & Datasheets
 DATA-SHEET 
DATASHEET
 
Product typeActuator
IP ratingIP54
Input Signal0..10 Vdc
ManufacturerBelimo
Power Supply24Vac/Vdc
Torque150 N
Running time140 to 150 sec
Actuator typeLinear

Find all parts for your ventilation system at iacs, the Free Delivery and 1-2 Delivery is available for all the Belimo Actuators in stock

The Belimo LH24A-SR100 is a type of Actuator used in HVAC and ventilation systems.

The force applied by the Torque of the LH24A-SR100 is 150 N.

This Rotary Actuator needs to be supported by a power supply of 24Vac/Vdc.

The ideal Belimo Actuators for your system are most affordable at iacs.

If you have questions concerning size or installation, refer to the Belimo custom datasheet above or email iacs for individualised support.

LH24A-SR100 - Linear actuator with rack 150 N, 150s/100 mm constant AC / DC 24 V

•   modulating Stroke range 0...100 mm
•   IP 54, Manual override by means of push-button
•   Control DC 0...10 V
•   Operating range DC 2...10 V
•   Position feedback DC 2...10 V
•   Connection PVC cable 1m

Features


  • Mode of operation The actuator is controlled with a standard modulating signal of DC 0 ... 10 V and travels to the position defined by the control signal. Measuring voltage U serves for the electrical display of the damper position 0 ... 100% and as slave control signal for other actuators.

  • Manual override Manual operation is possible with the pushbutton (the gearing latch remains disengaged as long as the pushbutton is pressed or detented).

  • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.

•     Electrical data Nominal voltage AC 24 V, 50/60 Hz / DC 24 V
•     Power supply range AC/DC 19.2 ... 28.8 V
•     Power consumption In operation 1.5 W @ nominal force
•     At rest 0.5 W
•     For wire sizing 3 VA
•     Connection Cable 1 m, 3 x 0.75 mm2
•     Functional data Actuating force 150 N @ nominal voltage
•     Control Control signal Y DC 0 ... 10 V, input impedance 100 k
•     Operating range DC 2 ... 10 V (See also «Overview of types»)
•     Position feedback (Measuring voltage U) DC 2 ... 10 V, max. 1 mA
•     Position accuracy ±5%
•     Stroke See «Overview of types»
•     Direction of stroke at Y = 0 V Reversible with switch 1 resp. 0
•     Running time 150 s / 100 mm
•     Sound power level <35 dB (A)
•     Safety Protection class III Safety extra-low voltage     
•     Degree of protection IP54 in any mounting position
•     EMC CE according to 89/336/EEC 
•     Mode of operation Type 1 (to EN 60730-1)
•     Rated impulse voltage Supply 0.8 kV (to EN 60730-1) Control 0.8 kV (to EN 60730-1)
•     Control pollution degree 3 (to EN 60730-1)
•     Ambient temperature –30 ... +50°C
•     Non-operating temperature –40 ... +80°C
•     Ambient humidity 95% r.h., non-condensating
•     Maintenance Maintenance-free
•     Dimensions / Weight Dimensions See «Dimensions» on page 5
•     Weight See «Overview of types» on page 1